All installations and services must be performed by qualified service personnel.

Anti-Short Cycle Operation

To prevent compressor short cycling, a call for cooling will be ignored for four minutes after the
termination of any cooling call. The anti-short cycle delay is also in effect at power-up.

Heat Mode

When a call for heat ("W") is received from the thermostat, if the “Cool” mode is not already active, the “T-T”
terminal is energized and the blower on delay is started. The on-off pattern of DIP switch SW2 (positions 1
and 2) select one of four blowers on delay values (see Table 1). When the delay time has elapsed, a speed
value is read from DIP switch SW1 positions 1 through 3 (see the CFM Tables) and the blower is ramped up to
that speed. The 2-Stage control will be operated by t-stat through W1 and W2. For 2-stage control with a
single stage t-stat, call for heat will go through W2. When W2 is energized, low fire is activated for 15
minutes. If a call for heat still exists, high fire will be activated and will continue until the demand for heat has
been satisfied.

Counterflow units, in addition, will run at a low blower speed shortly after the burner is brought on. They will
continue at that speed until the delay time has elapsed.

The control remains in steady heat mode until the thermostat is satisfied. When the call for heat signal is
removed, the “T-T” terminal is de-energized and the blower off delay is started. The on-off pattern of DIP
switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 1). When the delay time
has elapsed, the blower is ramped toward zero.

Table 1: ON and OFF Blower Delay Time Switch Settings

DIP SWITCH 2 SECTION
STATE

BLOWER DELAY

TIMES

2 1

4

3

ON - SEC

OFF - MIN

OFF OFF

30

OFF ON

60

ON

OFF

120

Factory Set

ON ON

240

OFF

OFF

2

OFF

ON

4

ON

OFF

6

Factory Set

ON

ON

8


Motor Blower Speed

Three blower speed outputs are provided. A “G” call for fan will provide the Low speed only. A “W”
heat call will provide the Heat speed only. A “Y” cooling call will provide the Cool speed only.

In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the
input that was first initiated. In the case where the control is in a cooling mode with both “Y” and “W”
inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to
the control switching into a heating mode. In the case where the control is in a heating mode with both
“Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be
executed prior to the control switching into a cooling mode. In the case where a call for fan “G” already
exists and either a “W” or a “Y” call is initiated, the blower speed will switch to the respective “W” or a
“Y” speed following the blower on delay for that call.
Six dip switches select Speed values for heat, cool, fan and dehumidification blower speeds (see the CFM
Tables).


Blower On and Off Delays

Four Heat blower on and four blower off delays are selected by two dip switches for each function. Refer
to Table 1 for specific delay values.