All installations and services must be performed by qualified service personnel.


Speed Selection values

Three dip switches select 8 cooling speeds. Dependant fan, and dehumidification speeds are selected by
the same switches, their tabular values are enacted when their function is called.
Three additional dip switches select 8 heating speeds which are enacted when heat is called. This allows
independent selection of heating and cooling capacity parameters. See the CFM Tables for speeds.


F. CFM TABLES

The following tables contain blower speed settings and their respective air flowrates for the ECM blower motor. To
change air flowrates from that of the shipped settings, use the respective SW1 dipswitch on the furnace’s integrated
control board (see Figure 2).

COOLING SPEEDS

HEATING SPEEDS & TEMPERATURE RISE

°F Rise

CFM

°F Rise

CFM

°F Rise

CFM

COOL

LOW

DEHUM

3-OFF

6-OFF

2-OFF

5-OFF

560

1-OFF

4-OFF

3-OFF

6-OFF

2-OFF

5-OFF

1-ON

4-ON

3-OFF

6-OFF

2-ON

5-ON

840

1-OFF

4-OFF

3-OFF

6-OFF

2-ON

5-ON

980

1-ON

4-ON

3-ON

2-OFF

6-ON

1-OFF

5-OFF

1120

3-ON

4-OFF

2-OFF

1-ON

Factory shipped

3-ON

settings

2-ON

1-OFF

3-ON
2-ON
1-ON

Operating Conditions
Are NOT Approved

700

2.5

1000

500

1400

700

3

1200

600

ALL UNITS

2

800

400

SW 1

switch

settings

Tons

CFM

4

3.5

SW1

switch

settings

OH2, OL2, OC2

OH5, OL5, OC5

OH11, OL11

82

636

75

696

69

756

63

828

82

966

1125

69

1148

77

1230

58

900

75

63

1260

84

1050

70

1350

56

1400

63

1500

1500

800

ADDITIONAL OH11, OL11 SETTINGS ONLY












12