MVI56E-MNET / MNETXT ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Interface Module
Page 116 of 181
ProSoft Technology, Inc.
April 23, 2014
Write Block
These blocks of data transfer information from the ControlLogix processor to the
module.
The following table describes the structure of the output image.
Write Block from Processor to Module
Word Offset
Description
Length
0
Write Block ID
1
1 to 200
Write Data
200
201 to 247
Spare
46
247
Select Priority Read Block
1
The Write Block ID is an index value used to determine the location in the
module’s database where the data will be placed. Each transfer can move up to
200 words (block offsets 1 to 200) of data.