ProSoft Technology MVI56E-MNET/MNETXT User Manual
Page 161

MVI56E-MNET / MNETXT ♦ ControlLogix Platform
Reference
Modbus TCP/IP Interface Module
User Manual
ProSoft Technology, Inc.
Page 161 of 181
April 23, 2014
Parameter
Value
Name
Enter a module identification string. Example: MNET_2
Description
Enter a description for the module. Example: M
ODBUS
TCP/IP
I
NTERFACE
M
ODULE
Comm Format
Select D
ATA
-INT.
Slot
Enter the slot number in the rack where the MVI56E-
MNET module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0
4 Select the Requested Packet Interval value for scanning the I/O on the
module. This value represents the minimum frequency that the module will
handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.