ProSoft Technology MVI56E-MNET/MNETXT User Manual
Page 21

MVI56E-MNET / MNETXT ♦ ControlLogix Platform
Start Here
Modbus TCP/IP Interface Module
User Manual
ProSoft Technology, Inc.
Page 21 of 181
April 23, 2014
Important: You must select the C
OMM
F
ORMAT
as D
ATA
-
INT in the dialog box, otherwise the
module will not communicate over the backplane of the ControlLogix rack.
4 Click OK
to continue.
5 Edit the Module Properties. Select the R
EQUESTED
P
ACKET
I
NTERVAL
value
for scanning the I/O on the module. This value represents the minimum
frequency at which the module will handle scheduled events. This value
should not be set to less than 1 millisecond. The default value is 5
milliseconds. Values between 1 and 10 milliseconds should work with most
applications.
6 Save the module.
Click OK
to close the dialog box. Notice that the module now appears in the
Controller Organization window.