ProSoft Technology MVI56E-61850S User Manual
Page 33

MVI56E-61850S ♦ ControlLogix Platform
Contents
IEC 61850 Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 33 of 81
September 4, 2014
Name
Description
Data Object
This value identifies the 61850 data object (DO) instantiated from a 61850 CDC to
which the data point is mapped.
The data object number has to be set within a specific range according to its data
type:
BOOL: 700000 to 709999
SINT: 800000 to 809999
INT: 810000 to 819999
DINT: 820000 to 829999
REAL: 900000 to 909999
Data Type
Type of the data as it resides in the internal database.
BOOL: Boolean / Bit
SINT: (Signed-8 bits) / Byte
INT: (Signed-16 bits) / Word
DINT: (Signed-32 bits) / Double word
REAL: (32-bit floating) / Double word
Point ID
Unique identifier for the Control point in the processor. It is a 16-bit value.
Control Mode
A code that selects the 61850 control mode according to IEC61850 specification:
Direct-with-normal-security
Sbo-with-normal-security, operate-once
Sbo-with-normal-security, operate-many
Direct-with-enhanced-security
Sbo-with-enhanced-security, operate-once
Sbo-with-enhanced-security, operate-many
SBO Timeout
*Only applicable for SBO control mode
The timeout in milliseconds for the control object to remain selected without receiving
an Oper or Cancel request
Comment
Comments cannot be edited