MVI56E-61850S ♦ ControlLogix Platform

Contents

IEC 61850 Server Communication Module

User Manual

ProSoft Technology, Inc.

Page 33 of 81

September 4, 2014

Name

Description

Data Object

This value identifies the 61850 data object (DO) instantiated from a 61850 CDC to
which the data point is mapped.
The data object number has to be set within a specific range according to its data
type:
BOOL: 700000 to 709999
SINT: 800000 to 809999
INT: 810000 to 819999
DINT: 820000 to 829999
REAL: 900000 to 909999

Data Type

Type of the data as it resides in the internal database.
BOOL: Boolean / Bit
SINT: (Signed-8 bits) / Byte
INT: (Signed-16 bits) / Word
DINT: (Signed-32 bits) / Double word
REAL: (32-bit floating) / Double word

Point ID

Unique identifier for the Control point in the processor. It is a 16-bit value.

Control Mode

A code that selects the 61850 control mode according to IEC61850 specification:
Direct-with-normal-security
Sbo-with-normal-security, operate-once
Sbo-with-normal-security, operate-many
Direct-with-enhanced-security
Sbo-with-enhanced-security, operate-once
Sbo-with-enhanced-security, operate-many

SBO Timeout

*Only applicable for SBO control mode
The timeout in milliseconds for the control object to remain selected without receiving
an Oper or Cancel request

Comment

Comments cannot be edited