ProSoft Technology MVI56E-61850S User Manual

Page 52

Advertising
background image

Contents

MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 52 of 81

ProSoft Technology, Inc.

September 4, 2014

4.2.4 MVI56E61850S.STATUS Tag

This array contains the overall module status.

MVI56E61850S.STATUS.

Description

ScanCounter

Scan counter increments at every module scan of the ladder logic

BackplanePhase

0 = Running
2 = Init/Initialize SoE/Control data from Processor
4 = InitTransfer PointIDs
6 = Init/Set clock
7 = InitWaiting Processor

ProductCode

Product Code 61S5

Firmware

Firmware version information

Backplane

Backplane statistics between the module and processor including read/write
data block counts, block error counts, DB, SoE, and Control block counts.

General

General diagnostics including initialization error, time-stamp module and
connection statistics.

Connection

Diagnostics for each of the 8 client connections including time-stamp, IP
address, and data packet status.

4.2.5 MVI56E61850S.UTIL Tag

The UTIL array is used for internal ladder implementation. Do not update or delete these
tags.