MVI56E-61850S ♦ ControlLogix Platform

User Manual

IEC 61850 Server Communication Module

Page 78 of 81

ProSoft Technology, Inc.

September 4, 2014

6.5

Connect to the Module

’s Web Page

The module's internal web server provides access to module status, diagnostics, and
firmware updates. If the module's IP address has already been assigned, simply enter in the
IP address into a web browser. If not, follow the steps below:

1 In ProSoft Configuration Builder, click the P

ROJECT

menu, then choose M

ODULE

>

D

OWNLOAD FROM

PC

TO

D

EVICE

. This opens the Download

dialog box.

2 In the Download dialog box, choose the connection type in the Select Connection Type

dropdown box:

o

Choose E

THERNET

if you are connecting to the module through the Ethernet cable.

o

Choose 1756

ENBT if you are connecting through CIPconnect or RSWho.

Refer to Connecting Your PC to the Module for more information.

3 In the Download files from PC to module dialog box, click B

ROWSE

D

EVICE

(

S

).

4 In ProSoft Discovery Service, right-click the MVI56E-61850S icon and choose V

IEW

MODULE

S WEBPAGE

from the shortcut menu.

This displays the module webpage.