6.5
Connect to the Module
’s Web Page
The module's internal web server provides access to module status, diagnostics, and
firmware updates. If the module's IP address has already been assigned, simply enter in the
IP address into a web browser. If not, follow the steps below:
1 In ProSoft Configuration Builder, click the P
ROJECT
menu, then choose M
ODULE
>
D
OWNLOAD FROM
PC
TO
D
EVICE
. This opens the Download
dialog box.
2 In the Download dialog box, choose the connection type in the Select Connection Type
dropdown box:
o
Choose E
THERNET
if you are connecting to the module through the Ethernet cable.
o
Choose 1756
ENBT if you are connecting through CIPconnect or RSWho.
Refer to Connecting Your PC to the Module for more information.
3 In the Download files from PC to module dialog box, click B
ROWSE
D
EVICE
(
S
).
4 In ProSoft Discovery Service, right-click the MVI56E-61850S icon and choose V
IEW
MODULE
’
S WEBPAGE
from the shortcut menu.
This displays the module webpage.