ProSoft Technology 5105-103M-PDPS User Manual

Page 100

Advertising
background image

Reference

5105-103M-PDPS ♦ ProLinx Gateway

User Manual

IEC 60870-5-103 Master to PROFIBUS Slave Gateway

Page 100 of 144

ProSoft Technology, Inc.

November 24, 2010

In Control Direction

Type

Description

6

time synchronization

7

general interrogation

10

generic data

20

general command

21

generic command

24

order for disturbance data transmission

25

ack for disturbance data transmission

List of Cause of Transmission Codes

In Monitor Direction

COT

Description

1

spontaneous

2

cyclic

3

reset frame count bit (FCB)

4

reset communication unit (CU)

5

start/restart

6

power on

7

test mode

8

time synchronization

9

general interrogation

10

termination of general interrogation

11

local operation

12

remote operation

20

positive ack of command

21

negative ack of command

31

transmission of disturbance data

40

positive ack of generic write command

41

negative ack of generic write command

42

valid data response to generic read command

43

invalid data response to generic read command

44

generic write confirmation

In Control Direction

COT

Description

8

time synchronization

9

initiation of general interrogation

20

general command

31

transmission of disturbance data

40

generic write command

42

generic read command

Advertising