3.4.19 Generic functions in control direction

INF

Semantics



<240>

Read headings of all defined groups



<241>

Read values or attributes of all entries in one group



<243>

Read directory of a single entry



<244>

Read value or attribute of a single entry



<245>

General interrogation of generic data



<248>

Write entry



<249>

Write entry with confirmation



<250>

Write entry with execution



<251>

Write entry abort

3.4.20 Basic application functions

⌧

Test mode

⌧

Blocking of monitor direction



Disturbance data



Generic services

⌧

Private data (if ASDU type is supported by module)

3.4.21 Miscellaneous

Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in

7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value. No

different rating shall be used in ASDU 3 and ASDU 9, that is, for each

measurand there is only one choice.

Measurand Max. MVAL = rated value times

1,2

or

2,4

Current L

1

⌧

⌧

Current L

2

⌧

⌧

Current L

3

⌧

⌧

Voltage L

1-E

⌧

⌧

Voltage L

2-E

⌧

⌧

Voltage L

3-E

⌧

⌧

Active power P

⌧

⌧

Reactive power Q

⌧

⌧

Frequency f

⌧

⌧

Voltage L

1

- L

2

⌧

⌧