Step 5: Monitor Point Configuration (Monitor Direction)
When a slave receives a Class 1 or Class 2 request from the master, it responds

with a message containing data. Each piece of equipment is normally configured

to respond with specific points when it is being polled with a Class 2 request.

During a Class 2 response, the slave may set a control bit (ACD) to inform the

master that there are new events to be transmitted. Then, the master will send a

Class 1 poll to read the events from the slave.
The IEC 60870-5-103 protocol states that the data is transferred between the

master and slave using an ASDU (Application Service Data Unit) format. Each

format is given by:

Type Identification

Variable Structure Qualifier
Cause Of Transmission
Common Address of ASDU
Function Type
Information Number
Data…
Data…
…

Refer to the protection equipment specification for the following information about

each point:
 Type: Type of the message
 Function Type: Type of protection function
 Information Number: Point Identification
This information identifies each point in the configuration. You must configure the

points that will be updated in the module database when a Class 2 or Class 1

response containing data is sent from the slave. Refer to [IEC-103

M

ASTER

S

ESSION X

S

ECTOR

0] to configure each point.