Type 99 Regulator with Type 61HP (extra high pressure) Pilot

A2505

January 2008

Type 99

INLET PRESSURE

OUTLET PRESSURE

LOADING PRESSURE

ATMOSPHERIC PRESSURE

through the relief valve body (J) (Figure 4). Since

loading pressure needs to exceed outlet pressure

only moderately to stroke the main valve fully open,

a continued increase in loading pressure differential

extends the main diaphragm (E) and the pusher

post assembly (K) far enough to separate the bleed

valve (D) and the bleed orifice (H). This permits

quick dumping of excess loading pressure into the

downstream system.
With a decrease in loading pressure on top of the

main diaphragm (E), the main spring (B) exerts an

upward force on the diaphragm rod connected to the

main diaphragm (E), pulling it upward. This moves

the main valve toward its seat, decreasing flow to the

downstream system.
Diaphragm (G) in the pilot valve acts as a sealing

member for the loading chamber and as a balancing

member to diaphragm (F). These two diaphragms are

connected by a yoke so any pressure change in the

pilot chamber has little effect on the position of the pilot

valve. Therefore, the active diaphragm in the pilot is

(F) and the pressure on the top side of this diaphragm

opposes the force of the pilot control spring (A).

Monitoring Systems

Monitoring regulators serve as overpressure protection

devices to limit system pressure in the event of open

failure of a working regulator feeding the system. Two

methods of using Type 99 regulators in monitoring

systems are as follows:

Working Monitor

On a working monitor installation (Figure 4), the

control line of the monitoring pilot is connected

downstream of the working regulator. During

normal operation, distribution pressure causes

the monitoring pilot to stand wide open. Full pilot

supply pressure enters the working monitor pilot and

permits the working monitor regulator to control at its

intermediate pressure setting.
Open failure of the working regulator increases

distribution pressure as the working regulator goes

wide-open. Intermediate pressure is then ignored by

the monitoring regulator, which controls downstream

pressure at its own pressure setting (slightly higher

than the normal control pressure).

Figure 3. Schematic of Type 99 Regulator with Type 61HP (Extra High Pressure) Pilot

DOWnSTREaM

COnTROL LInE

B

g

K

E

a

FLangE

aDaPTOR

InLET PRESSURE

TUBIng COnnECTIOn

H

J

D

C

F

RELIEF

vaLvE

CaP

yOKE

LEg

yOKE

CaP

yOKE

CaP

RELay

vaLvE

54A2767-a

A2505

InLET PRESSURE

OUTLET PRESSURE

LOaDIng PRESSURE
aTMOSPHERIC PRESSURE

Type 99

A6469

January 2008

Type 99

INLET PRESSURE

OUTLET PRESSURE

LOADING PRESSURE

ATMOSPHERIC PRESSURE