this recommendation due to the pipe arrangement, it

may be better to make the control line tap nearer the

regulator outlet rather than downstream of a block

valve. Do not make the tap near any elbow, swage, or

nipple which might cause turbulence.
In many instances, it will be necessary to enlarge the

downstream piping to keep flow velocities within good

engineering practices. Expand the piping as close to

the regulator outlet as possible.

!

WaRnIng

Adjustment of the pilot control spring to 

produce an outlet pressure higher than

the upper limit of the outlet pressure

range for that particular spring can cause

personal injury or equipment damage 

due to bursting of pressure-containing

parts or the dangerous accumulation

of gases if the maximum actuator

emergency casing pressure in the

Specifications section is exceeded.  If the 

desired outlet pressure is not within the

range of the pilot control spring, install a

spring of the proper range according to

the Maintenance section.

Each regulator is factory-set for the pressure setting

specified on the order. If no setting was specified, outlet

pressure was factory-set at the midrange of the pilot

control spring. In all cases, check the control spring

setting to make sure it is correct for the application.

Startup

Key numbers are referenced in Figure 9 for a low or

high pressure pilot and in Figure 12 for an extra high

pressure pilot. With proper installation completed and

downstream equipment properly adjusted, perform the

following procedure while using pressure gauges to

monitor pressure.
1. Very slowly open the upstream block valve.
2. Slowly open the hand valve (if used) in the control

line. The unit will control downstream pressure

at the pilot control spring setting. See the

adjustment paragraph following these numbered

steps if changes in the setting are necessary during

the startup procedure.
3. Slowly open the downstream block valve.
4. Slowly close the bypass valve, if any.
5. Check all connections for leaks.

The only adjustment on the regulator is the reduced

pressure setting affected by the pilot control spring

(key 43, Figure 9 or 11). Remove the closing cap

assembly (key 46, Figure 9) and turn the adjusting

screw (key 45, Figure 9 or 11). Turning the adjusting

screw clockwise into the spring case increases the

controlled or reduced pressure setting. Turning

the screw counterclockwise decreases the reduced

pressure setting. Always replace the closing cap, if

used, after making the adjustment.

Shutdown

Isolate the regulator from the system. Vent the

downstream pressure first; then vent inlet pressure to

release any remaining pressure in the regulator.

Maintenance

Regulator parts are subject to normal wear and must be

inspected and replaced as necessary. The frequency

of inspection and replacement of parts depends on the

severity of service conditions or the requirements of

local, state, and federal rules and regulations.

!

WaRnIng

Avoid personal injury or damage to 

property from sudden release of pressure

or uncontrolled gas or other process fluid. 

Before starting to disassemble, isolate

the pilot or regulator from all pressure

and cautiously release trapped pressure

from the pilot or regulator. Use gauges to

monitor inlet, loading, and outlet pressures

while releasing these pressures.

On reassembly of the regulator, it is recommended

that a pipe thread sealant be applied to pressure

connections and fittings as indicated in Figures 7

and 9 and lubricant be applied to sliding and bearing

surfaces as indicated in Figures 7 and 9, and that an

anti-seize compound be applied to adjusting screw

threads and other areas indicated Figures 9 and 11.

actuator and Standard P590 Series Filter

This procedure is to be performed if changing the main

spring and spring seat for those of a different range,

or if inspecting, cleaning, or replacing any other parts.

Unless otherwise indicated, part key numbers for a

Type 99 regulator with low or high pressure pilot and