MODBUS REGISTERS

EATON Power Xpert

®

Gateway Series 1000 Card User’s Guide

S 164201670 Rev 1

61

For example, the AC Voltage between Phase A and Neutral is available
in register 4010. To read the AC Voltage in Phase A at Panel #1, set the
Modbus program to Unit ID 2 and register 4010:

IP: <IP address of PDU/RPP>
Unit ID: 2
Starting Register: 4010
Number of Registers: 2
Function Code: 04

To read the AC Voltage in Phase A at Panel #4, set the Modbus program
to Unit ID 5 and register 4010:

IP: <IP address of PDU/RPP>
Unit ID: 5
Starting Register: 4010
Number of Registers: 2
Function Code: 04

Table 5. Panel Summary Registers (FC 04)

Name

Register

Data Type

Bytes

Display Template

1000

UINT

2

Vendor Name

1001

STRING

64

Model Name

1033

STRING

64

Display Name

1065

STRING

64

Serial Number

1123

STRING

64

Device Volts Rating

1202

UINT

4

Number of Phases

1208

UINT

2

Asset ID

1324

STRING

128

Breaker Rating

1453

UINT

2

Breaker Warning

1456

UINT

2

Breaker Overload

1457

UINT

2

Neutral Current Alarm

1459

UINT

2

Enter Admin State

3047

UINT

2

Enter Operating State

3048

UINT

2

Enter Readiness State

3049

UINT

2

Enter Alarm State

3050

UINT

2

Enter Standby State

3051

UINT

2