OPERATION

Eaton

®

9130 UPS (700–3000 VA) User's Guide

S

164201718 Rev 2

www.powerware.com

40

User Settings

The following table displays the options that can be changed by the user.

Table 3. User Settings

Description

Available Settings

Default Setting

Change Language

[English] [French] [Spanish] [German]
[Russian]
Menus, status, notices, and alarms are in all
supported languages. UPS faults, Event Log
data, and settings are in English only.

English

User Password

[Enabled] [Disabled]
If Enabled is selected, the password is USER.

Disabled

Audible Alarms

[Enabled] [Disabled]

Enabled

Set Date and Time

NOTE Time is a 24-hour clock.

Set Year, Month, Day, Hours, Minutes
Date: yyyy/mm/dd
Time: hh:mm

2008/01/01
12:00

Signal Inputs

Setup: [Not Used] [Force Bypass]
[Remote Shutdown] [Delayed Shutdown]
[On Generator] [Building Alarm 1]
Active: [High] [Low]
See “Programmable Signal Inputs” on
page 59.

RS232-3: Not Used, High
cXSlot Serial: Delayed
Shutdown, High
cXSlot Signal: Remote
Shutdown, Low

Relay Configuration

[UPS ok] [On Bypass] [On Battery]
[Battery Low] [Ext. Charger On]
See “Relay Output Contacts” on page 58.

Standard: UPS ok
RS232-1: Battery Low
RS232-8: On Battery
cXSlot-K1: On Battery
cXSlot-K2: Battery Low
cXSlot-K3: UPS ok
cXSlot-K4: On Bypass

Serial Port Configuration

[1200 bps] [2400 bps] [9600 bps]
NOTE USB communication requires 9600 bps.

RS232: 9600 bps
cXSlot: 9600 bps

Control Commands from Serial Port

[Enabled] [Disabled]

RS232: Enabled
cXSlot: Enabled

Output Voltage

[100V] [110V] [120V] [127V] [Autosensing]
[200V] [208V] [220V] [230V] [240V]
[Autosensing]

120V (low voltage models)
230V (high voltage models)

Output Frequency

[50Hz] [60Hz] [Autosensing]

Autosensing

* See “Configuring Bypass Settings” on page 48.