SPECIFICATIONS

Eaton

®

9130 UPS (700–3000 VA) User's Guide

S

164201718 Rev 2

www.powerware.com

87

Table 22. Environmental and Safety (All Models)

120 Vac Models

208/230/240 Vac Models

Surge Suppression

ANSI C62.41 Category B3

(6 KV Ring and Combination)

EN 61000-2-2

EN 61000-4-2, Level 3
EN 61000-4-3, Level 2

EN 61000-4-4, Level 2 (also on signal ports)

EN 6100-4-5, Level 3 Criteria A

EN 61000-4-6, Level 2
EN 61000-4-8, Level 2

EN 6100-4-11

EMC Certifications

<1500 VA: FCC Class B, VCCI Class B,

EN 55022 Class B

>2000 VA: FCC Class A, VCCI Class A,

EN 55022 Class A

CE per IEC/EN 62040-2,

Emissions: Category C1,

Immunity: Category C2

EMC (Emissions)

IEC 62040-2:ed2:2005 / EN 62040-2:2006

Safety Conformance

UL 1778, IEC 62040-1-1, IEC 60950-1

Agency Markings

CE, UL, CUL, NOM

Operating Temperature

0°C to 40°C (32°F to 104°F) in Online mode, with linear derating for altitude

NOTE Thermal protection switches load to Bypass in case of overheating.

Storage Temperature

-20°C to 40°C (-4°F to 104°F) with batteries

-25°C to 55°C (-13°F to 131°F) without batteries

Transit Temperature

-25°C to 55°C (-13°F to 131°F)

Relative Humidity

5–90% noncondensing

Operating Altitude

Up to 3,000 meters (9,843 ft) above sea level

Transit Altitude

Up to 10,000 meters (32,808 ft) above sea level

Audible Noise

<50 dBA at 1 meter typical

Leakage Current

<1.5 mA