Eaton Electrical Powerware 9130 User Manual

Page 63

Advertising
background image

COMMUNICATION

Eaton

®

9130 UPS (700–3000 VA) User's Guide

S

164201718 Rev 2

www.powerware.com

55

When the communication cable is installed, power management
software can exchange data with the UPS. The software polls the UPS
for detailed information on the status of the power environment. If a
power emergency occurs, the software initiates the saving of all data
and an orderly shutdown of the equipment.

The cable pins for the RS-232 communication port are identified in
Figure 19, and the pin functions are described in Table 4.

3

8

7

9

1

6

2

4

5

Figure 19. RS-232 Communication Port (DB-9 Connector)

Table 4. RS-232 Communication Port Pin Assignment

Pin Number

Signal Name

Function

Direction from the UPS

1

DCD

Battery Low signal

1,3

Out

2

RxD

Transmit to external device

Out

3

TxD

Receive from external device

2

In

4

DTR

PnP from external device (tied to Pin 6)

In

5

GND

Signal common (tied to chassis)

6

DSR

To external device (tied to Pin 4)

Out

7

RTS

No connection

In

8

CTS

On Battery signal

1,3

Out

9

RI

+8-12 Vdc power

Out

1

Configurable; see the “Relay Configuration” setting in “User Settings” on page 40.

2

If Pin 3 receives a Low (+V) signal for >5 seconds, the UPS executes the command selected by the “Signal Inputs”

setting in “User Settings” on page 40.

3

When the selected condition is active, output signals on Pins 1 and 8 shift from Low (positive voltage) to High

(negative voltage). When the condition no longer exists, the output signal returns to Low.

Advertising