OPERATION

Eaton

®

9130 UPS (700–3000 VA) User's Guide

S

164201718 Rev 2

www.powerware.com

41

Table 3. User Settings (continued)

Default Setting

Available Settings

Description

Frequency Converter

[Enabled] [Disabled]
If Enabled, the UPS operates as a frequency
converter, with bypass operation and all
bypass-related alarms disabled.

Disabled

Overload Alarm Level

[10%] [20%] [30%] ... [100%]
These values affect alarm level only, not UPS
operation such as transfers or shutdown.

100%
Generates the Output Overload
alarm at the set level.

Transfer to Bypass When Overload*

[Immediate] [After Delay]
If Immediate, transfer occurs at load >102%.
If After Delay, transfer occurs according to
Table 19 on page 84.

Immediate

Power Strategy

[Normal] [High Efficiency]
See “Setting Power Strategy” on page 48.

Normal

Automatic Start Delay

[Disabled] [No Delay] [1s] [2s]...[32767s]
If Disabled, automatic restart is not allowed.
See “Configuring Load Segments” on page 49.

Load Segment 1: No Delay
Load Segment 2: No Delay

Automatic on Battery Shutdown

[Disabled] [No Delay] [1s] [2s]...[32767s]
Shutdown cancels if utility returns before the
delay expires. See “Configuring Load
Segments” on page 49.

Load Segment 1: Disabled
Load Segment 2: Disabled

Start on Battery

NOTE Utility must be present and
output enabled at initial UPS startup.

[Enabled] [Disabled]
After initial startup, battery voltage must
exceed 2.10 volts per cell to start on battery.

Enabled

Energy Saving Mode

[Disabled] [50W] [100W] ... [1000W]
UPS output is turned off if the UPS is on
battery and output power is below the
selected level.

Disabled

Remote Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

No Delay

Delayed Shutdown Delay

[No Delay] [1s] [2s]...[10800s]

120s

Behavior on Rectifier Input Loss

NOTE Available only in >3000 VA
UPSs with separate supply sources
for the rectifier and bypass inputs.

[Prefer Battery] [Prefer Bypass]
If Prefer Bypass, upon loss the UPS will
transfer to bypass in 3 seconds and remain as
long as bypass is available.

Prefer Battery

On Battery Notice Delay

[0] [1s] [2s]...[99s]

5s

* See “Configuring Bypass Settings” on page 48.