Communication options, Rs-232 and usb communication ports – Eaton Electrical Powerware 9130 User Manual

Page 62

Advertising
background image

COMMUNICATION

Eaton

®

9130 UPS (700–3000 VA) User's Guide

S

164201718 Rev 2

www.powerware.com

54

 Installing Communication Options and Control Terminals

To install the communication options and control terminals:

1.

Install the appropriate connectivity card and/or necessary cable(s)
and connect the cables to the appropriate location.

See Figure 18 and the following section, “Communication
Options,” for detailed information.

2.

Route and tie the cable(s) out of the way.

3.

Continue to “Operation” on page 37 to start up the UPS.

 Communication Options

The Eaton 9130 has serial communication capabilities through the USB
and RS-232 communication ports or through a connectivity card in the
available communication bay.

The UPS supports two serial communication devices according to the
following table:

Independent

Multiplexed

Communication Bay

USB

RS-232

Any connectivity card

Available

Not in use

Any connectivity card

Not in use

Available

NOTE You can configure relays, signal inputs, and the serial port baud rate through the
front panel menus (see Table 3
on page 40).

NOTE The communication speed of the USB port is fixed at 9600 bps.

RS-232 and USB Communication Ports

To establish communication between the UPS and a computer, connect
your computer to one of the UPS communication ports using an
appropriate communication cable (not supplied). See Figure 18 for the
communication port locations.

Advertising