Troubleshooting – APC Back-UPS BN450M User Manual

Page 6

Advertising
background image

Back-UPS BE425M/425M-LM, BN450M/450M-CA

6

Troubleshooting

Problem and Possible Cause

Solution

The Back-UPS will not turn on

The Back-UPS is not connected to AC power,

there is no AC power available at the wall outlet,

or the AC power is experiencing a brownout or

over voltage condition.

Make sure the power cord is securely connected to

the wall outlet, and that there is AC power available

from the wall outlet.Where applicable, check that

the wall outlet is switched on.

The Back-UPS is on, the POWER button alternated green-red and the unit emits a constant tone

• The battery is disconnected.

• The battery is near the end of useful life and

should be replaced.

• Remove AC power and refer to the section

“Connect the Battery” on page 2

.

• Refer to the section

“Battery Replacement” on

page 8

for details.

Connected equipment loses power

A Back-UPS overload condition has occurred.

Remove all nonessential equipment connected to

the outlets. One at a time reconnect equipment to

the Back-UPS.

Charge the battery for 24 hours to make sure it is

fully charged. If the overload condition still occurs,

replace the battery.

The Back-UPS battery is completely discharged. Connect the Back-UPS to AC power and allow the

battery to recharge for eight hours.

Connected equipment does not accept the step-

approximated sine waveform from the Back-

UPS.

The output waveform is intended for computers and

peripheral devices. It is not intended for use with

motor driven equipment.

The Back-UPS may require service.

Contact SEIT Technical Support for more solutions.

The POWER button is green and flashes twice every 2 seconds.

The Back-UPS is operating on battery power.

The Back-UPS is operating normally on battery

power. At this point the user should save all open

files, and shutdown the computer. When AC power

is restored the battery will recharge.

The POWER button flashes green in rapid succession.

The Back-UPS battery has approximately two

minutes of remaining runtime.

The battery is near a total discharge state. The user

should save all open files, and shutdown the

computer. When AC power is restored the battery

will recharge.

The Building Wiring Fault LED is red

The building wiring presents a shock hazard that

must be corrected by a qualified electrical.

Do not operate the Back-UPS. Call a qualified

electrician to correct the building wiring fault.

The Back-UPS has an inadequate battery runtime

• The battery is not fully charged.

• The battery is near the end of useful life and

should be replaced.

Leave the Back-UPS connected to AC power for

eight hours while the battery charges to full

capacity.

As a battery ages, the runtime capability decreases.

See

Troubleshooting

to order replacement batteries.

The alarm is on with a constant tone; outlets are normal but

POWER

button is not bright.

The UPS os on AC power but the power of the

connected equipment exceeds the rated power of

the UPS. If a power disruption is to occur at any

moment the UPS may not be able to power the

connected equipment. Power to the outlets will be

uninterrupted as long as AC power is present.

Disconnect devices from the UPS until the load is

less than the rated output of the UPS.

The alarm is on with a constant tone and the UPS is off.

• The UPS was on battery and the connected load

exceeded the rated load of the UPS.

Turn off the UPS. Disconnect all devices. Turn on

the UPS and reconnect the devices one at a time.

Advertising