Fixed and Drawout Magnum Transfer Switches

3.2.5 Drawout Mechanism
The drawout mechanism is described in detail in Section 6

(Figure 14).

Figure 14. Drawout Mechanism (Closed Transition Shown)

3.3 Voltage Selection Panel

3.3.1 North American Voltage Selection (120, 208, 240, 480,

and 600 V, 60 Hz)
The North American market voltage selection panel consists of

multi-tap transformers, contained in a steel case mounted in the

transfer switch enclosure (Figure 15). The cover has “teardrop”

holes for the screws to allow easy access to the transformers.

The voltage is selected by simply removing the wires from the

default primary taps of both transformers and installing them on

the primary taps for the desired voltage. Taps are provided for

120 to 600 Vac to satisfy any required North American market

application voltage. The factory default position is 600 Vac.

Figure 15. Voltage Selection Panel

Figure 16. North American Market Voltage Selection Terminals

(Shown Connected to the 120 Vac Taps).

3.3.2 International Voltage Selection (208, 220, 240, 380, 415,

and 600 V 50-60 Hz).
The international market voltage selection panel is a multi-tap,

enclosed transformer mounted in the transfer switch enclosure.

Seven front accessible voltage taps from 208 to 600 Vac satisfy

any required international market application voltage. A quick-

change capability from one voltage to another is provided by a

small disconnect plug. The factory default position is 600 VAC.

3.4 Logic Panel

The logic panel provides the intelligence and supervisory circuits

which constantly monitor the condition of both the Source 1 and

Source 2 power sources, thus providing the required intelligence

for transfer operations (Figure 17). Detailed information is pre-

sented in a separate document:

ATC-600 Instruction Book (IB ATS-I005 - open transition only)

ATC-800 Instruction Book (IB ATS-CI03 - closed transition only)

WARNING

WHEN CHANGING THE SELECTED VOLTAGE, THE POWER MUST BE

REMOVED FROM THE TRANSFER SWITCH AND THE WIRES MUST

BE MOVED ON THE TAPS OF BOTH TRANSFORMERS.