Fixed and Drawout Magnum Transfer Switches

Figure 7. Fixed Switching Device for the Magnum Transfer

Switch.

Figure 8. Drawout Switching Device Installed in the Magnum

Transfer Switch.

1.3.2 Magnum Drawout Switching Devices
The Magnum drawout switching device is a design having three

positions with the compartment door closed (CONNECT, TEST,

DISCONNECT) and one position out of its compartment on the

extendable carriage rails (REMOVE). The Magnum drawout

switching device is equipped with both primary and secondary dis-

connects to provide for the drawout functioning. The operating

mechanism is a two-step, stored energy mechanism, either manu-

ally or electrically operated. When withdrawn on the extendable

carriage rails, Magnum switching devices can be inspected, acces-

sory items added, and minor maintenance performed. The inside

of the compartment can also be inspected with the switching

device withdrawn on the extendable carriage rails.

Figure 9. Drawout Switching Device Fully Extended from the

Magnum Transfer Switch.

1.3.3 Magnum Fixed Switching Devices
The Magnum fixed type switching device differs from the drawout

version in that it has no levering device, primary disconnects, and

secondary disconnects.

Figure 10. Primary and Secondary Connections on a Magnum

Fixed Switching Device.

PRIMARY CONNECTIONS

SECONDARY CONNECTIONS