Effective: March 2007

Fixed and Drawout Magnum Transfer Switches

Figure 38. Transfer from Normal Switching Device to Normal Bypass Switching Device, Steps 5-6.

7.3.3 Source 1 to Source 2 Bypass (Open Transition Only)
The Source 1 switch can be isolated and bypassed by the follow-

ing sequence:

1. Move the generator selector switch to the RUN position

because the load needs to be energized from the Source 2

power source.

2. Make sure that the Source 2 power source is available.

3. Open the source/switching device.

4. Close the Source 2 bypass switching device manually. The

Source 2 bypass light will be illuminated.

5. Rack out the Source 1 switching device (see Section 6). The

Source 1 isolated light will illuminate.

6. Inspect and/or perform the needed maintenance on the

Source 1 switching device.

7. Rack in the Source 1 switching device (see Section 6). The

Source 1 switching device will automatically recharge when it

is in the CONNECT position. The Source 1 isolated light will

no longer be illuminated.

8. Open the Source 2 bypass switching device. The Source 2

bypass light will no longer be illuminated.

9. The Source 1 switching device is now back in automatic oper-

ation.

7.3.4 Source 2 to Source 1 Bypass (Open Transition Only)
The Source 2 switching device can be bypassed and isolated by

the following sequence:

1. Ensure that the Source 1 power is available since the load will

be energized from the Source 1 power source.

2. Move the generator selector switch to the OFF position to

avoid nuisance starting of the generator while work is being

performed on the Source 2 switching device.

3. Open the Source 2 switching device.

4. Close the Source 1 bypass switching device manually. The

Source 1 bypass light will illuminate.

5. Rack out the Source 2 switching device (see Section 6). The

Source 2 isolated light will illuminate.

6. Inspect and/or perform the needed maintenance on the

Source 2 switching device.

7. Rack in the Source 2 switching device (see Section 6). The

Source 2 isolated light will no longer be illuminated.

8. Open the Source 1 bypass switching device. The

Source 1 light will no longer be illuminated.

9. The switching device is now back in automatic operation.

Cutler-Hammer

Digitrip 3000

Operational

High Load

Communications
Trip

Time Overcurrent

Curve Shape

Pickup (x In)

Time Multiplier

Pickup (x In)

Time

Program

Phase

Ground

I

I

I

RMS Amperes

Settings/Test Time/Trip Cause

Test

Program

Test

Pickup (x In)

Instantaneous

Short Delay

Amp Demand

I

Cutler-Hammer

Phase

Phase

Phase

Phase

Ground

Digitrip 3000

Operatio

High

Commun

Time Overcurrent

Curve Shape

Pickup (x In)

Time Multiplier

Time

Program

Phase

Ground

RMS

Settings/Test
Time/Trip Cause

Short Delay

Cutler-Hammer

Digitrip 3000

Operational

High Load

Communications
Trip

Time Overcurrent

Curve Shape

Pickup (x In)

Time Multiplier

Pickup (x In)

Time

Program

Phase

Ground

I

I

I

RMS Amperes

Settings/Test Time/Trip Cause

Test

Program

Test

Pickup (x In)

Instantaneous

Short Delay

Amp Demand

I

Cutler-Hammer

Phase

Phase

Phase

Phase

Ground

Digitrip 3000

Operatio

High

Commun

Time Overcurrent

Curve Shape

Pickup (x In)

Time Multiplier

Time

Program

Phase

Ground

RMS

Settings/Test
Time/Trip Cause

Short Delay

5

Source 1

6

Advertising