Fixed and Drawout Magnum Transfer Switches

Figure 17. ATC-800.

3.5 Neutrals

All 2-pole and 3-pole transfer switches are equipped with 100%

rated neutral connections (Figures 18 and 19). Different lug con-

figurations are available (See Option 21A).

Figure 18. Neutral SE with Ground Fault.

Figure 19. Solid Neutral.

3.6 Features

Switch options, which are not part of the logic scheme, are avail-

able to meet a variety of other application requirements. Options

are numbered with an associated description. More detailed selec-

tions, which must be made within a specific option number, are

identified by letters. For available options associated with the

logic scheme, refer to the specific logic document associated with

the type of logic selected.

14. Relay Auxiliary Contacts
Provides Form “C” relay auxiliary contacts.
E. Source 1 Available: Provides one Form “C” relay auxiliary con-

tact. The relay is energized when Source 1 is available.

F. Source 2 Available: Provides one Form “C” relay auxiliary con-

tact. The relay is energized when Source 2 is available.

Load

Connections

Source

Connections

Ground

Connections

NOTICE

OPTIONS ARE UL LISTED, EXCEPT AS NOTED, WHEN SUPPLIED ON

UL LISTED SWITCHES. IF AN OPTION IS SELECTED WHICH IS NOT

UL LISTED, THE SWITCH WILL NOT HAVE A UL LABEL.

NOTICE

NOT ALL OPTIONS ARE AVAILABLE FOR ALL TRANSFER SWITCH

CONFIGURATIONS. IF IN DOUBT, CHECK PRICE LIST 29-920 FOR

THE AVAILABILITY OF OPTIONS FOR A SPECIFIC TRANSFER

SWITCH DESIGN. THE OPTION NUMBERS USED HERE CORRE-

SPOND TO THE NUMBERS USED IN THE PRICE LIST.