Page 24

Effective: March 2007

Fixed and Drawout Magnum Transfer Switches

Figure 32.Carriage Label Showing DISCONNECT, TEST, and

CONNECT Positions of the Recessed Cover.

6.1.2 Levering the Switching Device
The switching device is now ready to be levered. With the

switching device OPEN, the levering device access door can be

raised. The levering device is hand operated using a standard

3/8” square drive and ratchet, which is not provided (Figure 33).

As long as the access door is raised, the switching device is held

in the “trip free” condition. Begin by rotating the levering-in screw

to the full counter clockwise (DISCONNECT) position.

Figure 33.Levering and Position Indication.
Close the compartment door and begin levering the switching

device into its different positions using a clockwise ratcheting

motion. When the switching device is levered fully to the

DISCONNECT or CONNECT position, the levering shaft hits a hard

stop. Do NOT exceed 25 ft lb (33.9 Nm) of torque or the levering

mechanism may be damaged.

The position of the switching device within its compartment is

indicated by color coded position indicators (See

Figure 29 through 32):

Red=Connect;

Yellow=Test; and

Green=Disconnect.

To remove the switching device from its compartment, follow the

procedure just described using a counter clockwise ratcheting

motion.

6.2. Fixed Switching Device

The Magnum fixed type switching device differs from the drawout

version in that it has no levering device, primary disconnects, and

secondary disconnects (Figure 34). In addition, a fixed switching

device does not have a standard feature to hold the switching

device in a “trip free” position

Figure 34. Typical Magnum Fixed Switching Device.
Fixed switching device terminals have holes for making bolted hor-

izontal primary bus connections. Adapters are available for mak-

ing vertical primary bus connections. Secondary connections can

be made through standard terminal blocks or a special connector

compatible with the drawout switching device’s type secondary

connector. Both secondary connection devices are mounted at

the top front of the switching device.

Red

Yellow

Green

NOTICE

THE SWITCHING DEVICE CAN BE LEVERED WITH THE COMPART-

MENT DOOR OPEN OR CLOSED, BUT IT IS ADVISABLE TO CLOSE

THE DOOR PRIOR TO LEVERING.

NOTICE

THE SWITCHING DEVICE MECHANISM IS INTERLOCKED SUCH

THAT CHARGED CLOSING SPRINGS ARE AUTOMATICALLY DIS-

CHARGED IF THE SWITCHING DEVICE IS LEVERED INTO OR OUT OF

THE CELL. DISCHARGE TAKES PLACE BETWEEN THE DISCONNECT

AND TEST POSITION.