Montana installation instructions – Hearth and Home Technologies Montana-36 User Manual

Page 13

Advertising
background image

01/04

4039-150 Rev B

13

MONTANA INSTALLATION INSTRUCTIONS

Figure 11

Installing the Firestop Spacer

CAUTION:

Firestop spacers must be used whenever the

chimney penetrates a ceiling/floor area.

Figure 10

Assembling Chimney

Sections

WARNING!

Carefully follow the instructions for assembly of the

pipe and other parts needed to install this fireplace

system. Failure to do so may result in a fire,

especially if combustibles are too close to the

fireplace or chimney and air spaces are blocked,

preventing the free movement of cooling air.

4. Assemble Chimney Sections

Attach either a straight chimney section or an offset to the top

of the fireplace (depending on your installation requirement).

Chimney sections are locked together by pushing downward

until the top section meets the stop bead on the lower section.

The inner flue is placed to the inside of the flue section below

it. The outer casing is placed outside the outer casing of the

chimney section below it. See Figure 10.

5. Install Firestop Spacers

Mark and cut out an opening in the ceiling for the firestop

spacer being utilized (17” x 17” for an FS538, 17” x 26” for an

FS540). Frame the opening with the same dimension lumber

used in the ceiling joists.

Install the firestop spacer.
These firestop spacers are designed to provide the minimum

2” air space required around the chimney. In all situations,

the firestop spacers are to be nailed to the ceiling joists from

the bottom or fireplace side, EXCEPT when the space above

is an insulated ceiling or attic space. In this situation, the

firestop spacer must be nailed from the top side to prevent

loose insulation from falling into the required 2” air space

around the chimney. See Figure 11.

Advertising