3-7. Electrical Service Guide

Input Voltage

230 V − 60 Hz

220 V − 50 Hz

Input Amperes At Rated Output

47.5

Max Recommended Standard Fuse Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

50

Normal Operating

3

70

Min Input Conductor Size In AWG

4

12

Max Recommended Input Conductor Length In Feet (Meters)

87 (27)

Min Grounding Conductor Size In AWG

4

12

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

3-8. Connecting Input Power

Ref. 802 246-A

1

=GND/PE Earth Ground

4

1

3

2

Y Disconnect and lockout/tag-

out input power before instal-

ling receptacle.

Y Have only qualified persons

make this installation. See

rating label in Section 3-4, and

be sure to supply correct in-

put power.

1

Proper Receptacle

(NEMA 6-50R)

(User-Supplied)

Receptacle must comply with appli-

cable codes.
2

Input And Grounding

Conductors

See size and length using Section

3-7. Conductors must comply with

applicable codes.
3

Over-Current Protection

Select type and size of over-current

protection using Section 3-7.
4

Plug (NEMA 6-50P)

Connect plug to properly installed

receptacle.
Close and secure door on discon-

nect device. Remove lockout/tagout

device, and place switch in the On

position.