C. Sidewalls/Surrounds

Adjacent combustible side walls must be located a minimum of 12 in. (305 mm) from the fi replace opening. See Figure 3.3.
If you are using a decorative surround constructed of combustible material, it must be located within the shaded area de-
fi ned in Figure 3.3. Short stub walls are also acceptable if they are contained within the shaded area.

D. Frame the Fireplace

Figure 3.4 shows a typical framing (using 2 x 4 lumber) of the fi replace, assuming combustible materials are used. All re-
quired clearances to combustibles around the fi replace must be adhered to. See Figure 3.2. Any framing across the top of
the fi replace must be above the level of the top standoffs.

9-3/4 in.

(248 mm)

14-3/8 in.

(365 mm)

12 in.

(305 mm)

4 in.

(102 mm)

Brick

Front

Flush

Front

12 in.

(305 mm)

A
B

50 deg.

39 deg.

Figure 3.3 Sidewalls and Surrounds

23 in.

(584 mm)

41-1/2 in.

(1055 mm)

A

2 in. (51 mm)
min. air
clearance
to the
enclosure.

Note: Fireplace
header cannot be
positioned until
after the fireplace
assembly is in place.

41-1/2 in. (1055 mm)
header height.
Use only noncombustible
material below the top
of the front standoffs.

Figure 3.4 Framing the Fireplace

Model #

A

Fireplace Opening

B

Outside Dimensions

A36

in.

36

42

mm

914

1067

A42

in.

42

48

mm

1067

1219

Model #

A

A36

in.

43

mm

1092

A42

in.

49

mm

1245