Location of the fi replace and chimney will affect performance.
As shown in Figure 2.1 the chimney should:

• Be installed through the warm airspace enclosed by the

building envelope. This helps to produce more draft,
especially during lighting and die-down of the fi re.

• Penetrate the highest part of the roof. This minimizes the

effects of wind turbulence.

• Be located away from trees, adjacent structures, uneven

roof lines and other obstructions.

Offsets can restrict draft so their use should be minimized.
Consider the fi replace location relative to fl oor and ceiling
and attic joists.

Recommended

Location

Marginal
Location

Location

Not

Recommended

Recommended

Location

Multi-level Roofs

Windward

Leeward

Outside Air Intake

Location

Not

Recommended

Figure 2.1 Recommended Chimney Locations