Caution, Warning, A. chimney requirements – Hearth and Home Technologies A42CH EN User Manual

Page 17: Table 5.1

Advertising
background image

Heatilator • A36C & A42C • 28396 Rev Y • 10/06

17

A. Chimney Requirements

Vertical distances are measured from the base of the fi re-
place as shown in Figure 5.2.

To determine the chimney components needed to complete
your particular installation, follow the steps below:

• Determine the total vertical height of the fireplace

installation. This dimension is measured from the base of
the fi replace assembly to the point where the smoke exits
the termination cap.

• Subtract the effective height of the fi replace assembly from

the overall height of the fi replace installation (measured
from the base of the fireplace to the bottom of the
termination cap).

• Refer to Table 5.1 to determine what components must

be selected to complete the fi replace installation.

• Determine the number of ceiling fi restops, stabilizers,

roof flashing, etc. required to complete the fireplace
installation.

6 ft (1.8 m) max.
unsupported
run
20 ft (6.10 m) max.
pipe between an
offset & return

Ceiling firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

16.5 ft (5.03 m) min. height/single offset-return

20 ft. (6.10 m) min. height/double offset-return

90 ft (27.4 m) max. height

6 ft (1.83 m) max.
unsupported chimney
above roof

41-1/4 in.

(1048 mm)

Effective

Height

Figure 5.2 Chimney Requirements

Table 5.1

• Do NOT connect this fireplace to a chimney flue

servicing another appliance.

• Do NOT connect to any air distribution duct or

system.

CAUTION

Fire Risk
• Must maintain 2 in. (51 mm) air clearance

to insulation and other combustible
materials.

WARNING

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL3

4-3/4

121

Ceiling Firestops

FS338

0

0

FS339

0

0

FS340

0

0

Offsets/Returns

SL315

13-3/8

340

SL330

15-1/2

394

Roof Flashing

RF370

0

0

RF371

0

0

Chimney Sections*

SL306

4-3/4

121

SL312

10-3/4

273

SL318

16-3/4

425

SL324

22-3/4 578

SL336

34-3/4 883

SL348

46-3/4 1187

* Dimensions refl ect effective height.

• Minimum overall straight height

16.5 ft

(5.03 m)

• Minimum height with offset/return

16.5 ft

(5.03 m)

• Maximum height

90 ft

(27.43 m)

• Maximum chimney length between an offset

and return

20 ft

(6.1 m)

• Maximum distance between chimney stabiliz-

ers

35 ft

(10.67 m)

• Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length be-

tween the offset and return

6 ft

(1.83 m)

• Maximum unsupported chimney height above

the fi replace

35 ft

(10.67 m)

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

Note: A maximum of two pairs of offsets and returns may
be used.