AC Power Measurements

1Φ KW, KVA, KVAR, Power Factor & Phase Angle Measurement
1. Set the rotary switch to the ‘KW/KVA’

position.

2. Insert the test leads to the meter as

follows: Black to ‘COM’ and Red to ‘V’.

3. Connect the black lead to the neutral line.
4. Connect the red lead to the power line

and clamp onto the same lead to which
the red lead is connected.

5. The meter selects the best range

automatically.

6. Select the desired display combination

using the RANGE key. Press RANGE to
scroll through the following combination displays:

ƒ

kW and HP (horsepower)

ƒ

kW and PF (power factor)

ƒ

kW and KVAR (reactive power)

ƒ

KVA and phase angle (θ)

ƒ

V and A

Note that LEAD and LAG icons are also displayed on the LCD to inform the user that the voltage is
leading or lagging the current with regard to phase.
Note: Allow 2 seconds after each RANGE key press for the meter to update the display.

1 HP = 746 Watts

PF

KW

KVA

=

= cosθ

KVA (Apparent Power) = (V*A) / 1000

KVAR (Reactive Power) =

(KVA)

(KW)

2

2

= KVA * sinθ

NOTES
1. The ‘+’ sign printed on the meter must face the power source for best accuracy.

2. If the device under test is a switching mode power supply, the KW, PF, and Phase angle

measurements may not be accurate.