Hobart Welding Products ARCSTAR 280 NT User Manual

Page 24

Advertising
background image

OM-4402 Page 20

SECTION 6 – OPERATING AUXILIARY EQUIPMENT

6-1.

Auxiliary Power Receptacles And Circuit Breakers

Ref. 198 912

1

4

2

5

3

Y

If unit does not have GFCI re-
ceptacles, use GFCI-
protected extension cord.

.

Auxiliary power decreases as
weld current increases..

1

240 V 50 A AC Receptacle
RC1

RC1 supplies 60 Hz single-phase
power at weld/power speed. Maxi-
mum output is 8 kVA/kW.

2

120 V 20 A AC Duplex
Receptacle RC2

3

120 V 20 A AC Duplex
Receptacle RC3

RC2 and RC3 supply 60 Hz single-
phase power at weld/power speed.
Maximum output from RC2 or RC3 is
2.4 kVA/kW.

4

Circuit Breakers CB1 and CB2

CB1 and CB2 protect RC1 from over-
load. If CB1 or CB2 opens, RC1 and
one of the 120 volt receptacles does
not work. 120 volts may still be pres-
ent at RC1.

5

Circuit Breaker CB3

6

Circuit Breaker CB4

CB3 protects RC2 and CB4 protects
RC3 from overload. If a circuit break-
er opens, the receptacle does not
work.

.

Press button to reset circuit
breaker. If breaker continues to
open, contact Factory
Authorized Service Agent.

Combined output of all receptacles
limited to 8 kVA/kW rating of the gen-
erator.

EXAMPLE: If 20 A is drawn from
each 120 V duplex receptacle, only
13 A is available at the 240 V
receptacle:

2 x (120 V x 20 A) + (240 V x 13 A) =
8 kVA/kW

6

Watts

Weld Current

Amperes

250
225
200
150
100

50

0

3500
4260
5140
6700
8000
8000
8000

31
39
46
60

62.4
62.4
62.4

15.5

19
23
30

31.2
31.2
31.2

Simultaneous Welding And Auxiliary Power

Output

240 V

Receptacle

Amperes

120 V

Receptacle

Amperes

Advertising