Covered alcove applications – Hearth and Home Technologies 6000GL-IPILP-S User Manual

Page 22

Advertising
background image

Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S • 2102-900 Rev. O • 12/08

22

O

N

P

R

Q

V

= VENT TERMINAL

X

= AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

Figure 6.3 Minimum Clearances for Termination

A

= 12 inches.................clearances above grade, veranda,

porch, deck or balcony

B =

12

inches.................clearances to window or door

that may be opened, or to perma-
nently closed window. (Glass)

C

= 18 inches.................vertical clearance to unventilated

soffi t or to ventilated soffi t located
above the terminal

30 inches .................for vinyl clad soffi ts and below

electrical service

D

= 9 inches...................clearance to outside corner

E

= 6 inches...................clearance to inside corner

F

= 3 ft. (Canada) ..........not to be installed above a gas

meter/regulator assembly within 3
feet (90 cm) horizontally from the
center-line of the regulator

G =

3

ft

...........................clearance to gas service regulator

vent outlet

H

= 9 inches (U.S.A.)

12 inches (Canada) clearance to non-mechanical

air supply inlet to building or the
combustion air inlet to any other
appliance

i

= 3 ft. (U.S.A.)

6 ft. (Canada) ...........clearance to a mechanical (pow-

ered) air supply inlet

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.

** a vent shall not terminate directly above a sidewalk or paved driveway

which is located between two single family dwellings and serves both
dwellings.

*** only permitted if veranda, porch, deck or balcony is fully open on a

minimum of 2 sides beneath the fl oor, or meets Note 2.

Note 1: On private property where termination is less than 7 feet above a
sidewalk, driveway, deck, porch, veranda or balcony, use of a listed cap
shield is suggested. (See vents components page)

Note 2: Termination in a covered alcove space (spaces open only on one
side and with an overhang) are permitted with the dimensions specifi ed
for vinyl or non-vinyl siding and soffi ts. 1. There must be 3 feet minimum
between termination caps. 2. All mechanical air intakes within 10 feet
of a termination cap must be a minimum of 3 feet below the termination
cap. 3. All gravity air intakes within 3 feet of a termination cap must be a
minimum of 1 foot below the termination cap.

(See Note 1)

(See Note 2)

Note 3: Local codes or regulations may require different
clearances.

Note 4: Termination caps may be hot. Consider their proximity to
doors or other traffi c areas.

Note 5: Location of the vent termination must not interfere with
access to the electrical service.

In the U.S and Canada: Vent system termination is NOT permitted
in screened porches.

Vent system termination is permitted in porch areas with two or more
sides open. You must follow all side walls, overhang and ground
clearances as stated in the instructions.

Heat & Glo assumes no responsibility for the improper performance
of the appliance when the venting system does not meet these
requirements.

C

J

B

D

i

B

F

G

B

A

A

E

X

V

V

V

V

V

V

V

M

U.S

(3 FT.)

H or i

Electrical

Service

V

K

V

K

V

L

C

V

M*** = 18 inches .............clearance under veranda, porch,

deck, balcony or overhang

42

inches

......... vinyl

N

= 6 inches ........... non-vinyl sidewalls

12 inches ......... vinyl sidewalls

O

= 18 inches ......... non-vinyl soffi t and overhang

42 inches ......... vinyl soffi t and overhang

P =

8

ft.

Q

MIN

R

MAX

1 cap

3 feet

2 x Q

ACTUAL

2 caps

6 feet

1 x Q

ACTUAL

3 caps

9 feet

2/3 x Q

ACTUAL

4 caps

12 feet

1/2 x Q

ACTUAL

Q

MIN

= # termination caps x 3 R

MAX

= (2 / # termination caps) x Q

ACTUAL

Covered Alcove Applications

(See Note 1)

(See Note 5)

(See Note 5)

J** = 7

ft.

.........................

c l e a r a n c e a b o v e p a v e d
sidewalk or a paved driveway
located on public property

K

= 6 inches................. clearance from sides of electri-

cal service

L =

12

inches................

clearance above electrical
service

Measure horizontal clearances from this surface.

Measure vertical clearances from this surface.

(See Note 2)