4/01

Specifications

Introduction

The following tables contain electrical, physical, safety and performance specifications for the UMC800
controller.

Controller Design

Parameter

Description

Controller

CPU with two serial communication ports,* power supply, and backplane assembly.
Capable of supporting up to 16 input /output modules.

*CPU option provides additional RS 485 communications with Modbus RTU protocol.

I/O Module Configuration

Component

Parameter

Description

Input Types

mV, V, mA, T/C, RTD, Ohms

Universal Analog Inputs

(Module ID 1)

Number of Inputs

4 per module, up to 16 modules per controller (64 inputs)

Signal Source

Thermocouple with cold junction compensation
Line resistance up to 1000 ohms, T/C, mV, mA, V
RTD Pt 100 ohms, 3-wire connections, 40 ohms balanced
maximum

Input Impedance

10 megohms for T/C and mV inputs; >1 megohm for volt
inputs

Input Isolation

400 Vdc point-to-point
3.75K Vac RMS A/D converter to logic

Stray Rejection

Series mode >60 dB. Common mode at 120 Vac >130 dB.

Burnout

T/C, mV, V (except following ranges) configurable to
upscale, downscale, or none.

Volt: –500 mV to 500 mV; –1 V to 1 V; –2 V to 2 V; –5 V to
5 V; 0 V to 10 V; –10 V to 10 V; inherent to zero volt

RTD: Inherent upscale

mA: Inherent downscale

T/C Break Detection

Via current pulse