Specifications
I/O Module Configuration

94

UMC800 Controller Installation and User Guide

Release F

4/01

Component

Parameter

Description

Accuracy (at reference
conditions)

Factory configured accuracy = ± 0.1 % of range
Cold junction accuracy = ± 0.5 °C
Field calibration accuracy = ± 0.05 % of range

Reference conditions:

Temperature = 25 °C ± 3 °C (77 °F ± 5 °F)
Humidity = 10 % to 55 % RH non-condensing
Line voltage = Nominal ± 1 %
Source resistance = 0 ohm
Series mode and common mode = 0 V
Frequency = Nominal ± 1 %

A/D Converter
Resolution

Better than 1 part in 50,000 at 50 Hz.
Better than 1 part in 41,667 at 60 Hz.

Temperature Effect on
Accuracy

0.15 % per 10 °C in the rated limits

Long Term Stability

0.1 % per year

Number of Outputs

4 per module (isolated), up to 4 modules per controller (16
outputs)

Analog Outputs

(Module ID 2)

Isolation from Logic

3.25 K Vac RMS

Accuracy

Factory configured accuracy = 0.1 % at reference conditions
Field calibration accuracy = 0.1 %

Temperature Effects

0.1 % per 10 °C in the rated limits

D/A Resolution

16 bits

Digital Inputs

AC Inputs

(Module ID 5)

DC Inputs

(Module ID 4)

Inputs per Module

6

6 (sink/source)

Input Voltage Range

80 Vac to 264 Vac

10.2 Vdc to 26.4 Vdc

Peak Voltage

264 Vac

26.4 Vdc

AC Frequency

47 Hz to 63 Hz

N/A

ON Voltage Level

75 Vac minimum

9.5 Vdc minimum

OFF Voltage Level

20 Vac maximum

3.5 Vdc maximum

Input Impedance

12K @ 60 Hz

2.7 K

Input Current

13 mA @ 100 Vac, 60 Hz
11 mA @ 100 Vac, 50 Hz

4.0 mA @ 12 Vdc
8.5 mA @ 24 Vdc

Minimum ON Current

5 mA

3.5 mA

Maximum OFF Current

2 mA

1.5 mA

Base Power Required *

50 mA maximum

50 mA maximum

OFF to ON Response

5 ms to 30 ms

1 ms to 8 ms

ON to OFF response

10 ms to 50 ms

1 ms to 8 ms