Ao module, Ai module, Backplane cpu – Honeywell UMC800 User Manual

Page 74

Advertising
background image

Maintenance
Controller Calibration

66

UMC800 Controller Installation and User Guide

Release F

4/01

Factory calibration

Factory calibration of controller components is performed before shipment to 0.1% accuracy. Calibration
values are contained in a number of the controller components, namely: the CPU, Backplane, and AI and
AO modules.

Figure 32 shows the various components in which calibration data is stored.

Calibration functions and parameters for the user interface are stored in memory on the CPU.

Each AI module contains two (2) cold junction compensation (CJC) references that are factory
calibrated. Factory calibration data for the CJC references is stored in a non-volatile memory on the AI
module.

Field calibration values for the AI modules (both zero offset and span calibration and CJC reference
values) are stored on the CPU.

Factory calibration values (zero offset and span corrections) for AO modules are stored in non-volatile
memory on the AO module and can be changed only if the write protect jumper is not cut. See Write
Protect Jumper ST1
.

The gains and offsets of the preamp are factory calibrated and the calibration data is stored in a non-
volatile memory on the backplane. No field calibration of these values is possible.

Write Protect Jumper ST1

ATTENTION

A jumper (ST1) on the AO module PWA can be cut to prevent changes to calibration values.
This will write protect the AO and prevent further calibration of these values.

AO Module

AO01

AO02

AO03

AO04

Factory

& Field

Calibration

Values

ST1

AI Module

AI01

AI02

AI03

AI04

CJC Factory

Calibration

Values

CJC

CJC

Factory Calibrated

Preamp Gains and Offsets

(for AI and CJC)

Backplane

CPU

Calibration

Function

Calibration

User Interface

Field

Calibration

Values

(AI and CJC)

in Battery-backed RAM

Figure 32 Controller components that contain calibration values