Honeywell UMC800 User Manual

Page 33

Advertising
background image

Mounting and Wiring

Signal Wiring

Release F

UMC800 Controller Installation and User Guide

25

4/01

Analog inputs (module ID 1)

A universal Analog Input module accepts a variety of input signals from field devices as summarized in
Table 9. Figure 13 illustrates the terminal block connections for the various inputs. See Specifications
section for more details on all I/O module specifications. One AI module can be configured to accept
multiple input types.

Table 9 Universal analog input module specifications

Specification

Description

Input Types

mV, V, mA, T/C, RTD, and Ohms

Number of Inputs

4 per module, up to 16 modules per controller (64 inputs)

Signal Source

Thermocouple with cold junction compensation, for operation between 32 °F to
176

°

F (0 °C to 80 °C)

Line resistance up to 1000 ohms, T/C, mV, mA, V
RTD Pt 100 3-wire connections, 40 ohms balanced max.

Input Impedance

10 Megohms for T/C, mV inputs,
> 1 Megohms for volt inputs

12

11

10

9

8

7

6

5

4

3

2

1

1

Channel 4

Channel 3

Channel 2

Channel 1

+

-

RTD

+

-

RTD

+

-

RTD

+

-

RTD

+

-

Thermocouple Input

T/C, mV, V

Ground Terminal

+

-

Ground Terminal

RTD

RTD Input (3 wires)

+

-

Current Input mA

* A 250 ohm resistor is required for
the input range.

*

Ground Terminal

4 to 20

mA

Source

+

-

mV, V Inputs

Ground Terminal

mV or V

Source

Field Wiring

Figure 13 AI module terminal block connections