Burner Control/Flame Safety

Electrical Installation

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

23

7/08

Output Signal Connections

0/4-20 mA, 0/1-5 Vdc Feedback Signal Connections

ATTENTION

Shielded and grounded cables are recommended.

Actuator output is a 4 to 20 mA analog signal. If a voltage input is required for customer devices, a range
resistor is needed at the device input. Refer to (page 19) for more information.

Slidewire Emulator Connections

ATTENTION

Shielded and grounded cables are recommended.

If you ordered the Slidewire output option for your actuator, it is set at the factory to provide an output that
emulates 100 to 1000 ohm slidewires. Refer to (page 19) for more information.

Burner Control/Flame Safety

Introduction

Often, Gas Fired control applications use a Flame Safety System that drives the gas valve to full closed and full
open during the start-up sequencefor the burner. HercuLine® 2000 Series actuators have been designed to be
compatible with the Flame Safety Systems and to perform the required operations.

Configuration

In the Input Set Up Group (Page 39), configure the parameter FSTYPL to Down .
In the Digital Input Set Up group (Page 51), configure the parameter DIG INP to Up.

Wiring

Figure 13 Burner Control/Flame Safety Wiring shows a Typical Flame Safety Module wiring diagram.

+ –

1

2

3

4

5

6

7

8

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

1

2

2

3

3

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

Typical Flame

Safety Module

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

2

3

4

5

6

7

8

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

1

2

2

3

3

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

Typical Flame

Safety Module

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

4

+ –

1

2

3

4

5

6

7

8

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

1

2

2

3

3

+ –

1

2

3

4

5

6

7

8

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

1

2

2

3

3

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

Typical Flame

Safety Module

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

2

3

4

5

6

7

8

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

Typical Flame

Safety Module

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

2

3

4

5

6

7

8

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

1

1

2

2

3

3

4

4

5

5

6

6

7

7

8

8

9

9 10

HercuLine TB3

Add Jumper

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

+ –

1

1

2

2

3

3

+ 4 to 20 Output from Controller

– 4 to 20 Output from Controller

Typical Flame

Safety Module

To TB3 #10

To TB3 #5

Modulate

High Fire

Common

Low Filter

4

Figure 13 Burner Control/Flame Safety Wiring