Display set up group, Table 18 display set up group parameters – Honeywell HERCULINE 2000 User Manual

Page 60

Advertising
background image

Set Up and Calibration Procedures
Display Set Up Group

52

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Display Set Up Group

Table 18 lists the parameters and selections availible for the SET DISPLAY group.

Table 18 Display Set Up Group Parameters

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

DECMAL


8888

888.8

default = 8888

DECIMAL POINT LOCATION

— This selection determines

where the decimal point appears in the display.

None



One Place

Note: Be sure the selection agrees with the value to be
displayed. If display value requires 4 whole digits, the
decimal will not show.

EUNITS

PCNT

DEG

default = PCNT

UNITS DISPLAY

— Selects the units of the position display.

Percent

— Shows actuator position as a percentage of span.

(0 to 100%)

Degrees

— Shows the actuator position in degrees of

rotation. (0 to 150

°) (90°)

UNITS


SI

ENGL

default = ENGL

DISPLAY UNITS

— Selects standard for unit values for the

local display.

SI

— Display will show unit values in international (metric)

units. (Temperature in degrees C, Date format: ddmmyy)

English

Display will show unit values in U.S. units.

(Temperature in degrees F, Date format: mmddyy)