Set Up and Calibration Procedures

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

61

7/08

Actuator Lower

Display
Prompt

Selections or

Range of Setting

Parameter Definition/PDA HercuLink

®

Prompt

PDA users: The prompts are organized differently on your PDA’s

HercuLink

®

software. Grayed prompts are under Configuration, Maintenance. Non-grayed

prompts are under Maintenance.

LD CAL

NONE

INP

MTR

COUT

ALL

POS

default = NONE

RESTORE CALIBRATION TYPE

— Allows you to restore a

calbration value to its factory calibration.

Input

— Restores input calibration to the factory calibration

for the current configured input type.

Motor

— Restores motor calibration to the factory calibration.

Output

— Restores actuator output calibration to the factory

calibration for the current configured output type.

All

— Restores input (for the type configured), motor and

output (for the type configured) calibration to the factory
calibration.

POS

— Allows a position sensor field calibration to be stored

as a factory calibration. This is to be used when a sensor is
replaced in the field. See “Calibrate POS Output”.

LD CFG

DIS

ENAB

default = DIS

RESTORE DEFAULT FACTORY CONFIGURATION

Allows you to restore the factory default configuration.

DIS

— Restore disabled.

ENAB

— Restore enabled.

RESTRT DIS

ENAB

default = DIS

SYSTEM RESTART

— Allows you to force the system to

restart.

DIS

— Restart disabled.

ENAB

— Restart enabled.

Note: The MANRST function must be set to SYST.

* Temperature units are displayed in degrees C or F, and are set by the UNITS parameter. See SET
DISPLA set up group.

† Note that the upper display contains the parameter name and the lower display contains the value.
This is to allow for the display of hours: minutes: seconds.