Set Up and Calibration Procedures
Calibration

66

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

7/08

Calibration Set up

Follow the steps below to set up the test equipment and actuator to verify calibration or perform calibration
procedures.

Step

Action

1

Determine input type (current or voltage).

2

Set jumper W2 on main CPU board according to type of signal source. See Figure 27 on page
68 for jumper location.

3

Connect the copper leads from the signal source to the input terminals of the actuator as
shown in Figure 25.

4

Place signal source output at zero and switch power on.

5

Connect a 250 ohm resistor across the Output terminals of the actuator and connect the DVM
leads to the terminals.

Actuator

Input

5 4

-

+

Output

2 1

-

+

+

-

Calibrated
Signal
Source

Digital
Voltmeter

+ -

Terminal Block

Internal 250 ohm resistor

settable through

Jumper W2

Current

Voltage

250 ohm
resistor
(supplied)

Figure 25 Calibration Wiring Connections (non-slidewire emulation)