Set Up and Calibration Procedures

Calibration

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

73

7/08

Table 28 Slidewire Emulation Calibration Procedure

Step

Operation

Press

Result

1

Enter Calibration
Mode

SETUP

until you see

Upper Display

=

CAL

Lower Display

=

OUTPUT

FUNCTION

Upper Display

=

DIS

Lower Display

=

CALOUT

or

key

Upper Display

=

BEGN

Lower Display

=

CALOUT

2

Calibrate Zero (0%)

FUNCTION

Upper Display =

xxx

Lower Display =

ZERO

xxx = arbitrary number assigned by software

or

key

Adjust actuator output voltage using down key until value on
DVM ceases to change, then press up key until value on DVM
moves up one digit

3

Calibrate Span
(100%)

FUNCTION

Upper Display

=

xxxx

Lower Display

=

SPAN

xxx = arbitrary number assigned by software

or

key

Adjust actuator output voltage using

key until value on DVM

ceases to change, then press

down key until value on DVM

moves down one digit

FUNCTION

Calibration for zero and span output values are now stored.

Slidewire Emulation Output Calibration is complete. Read meter
connected to actuator output.

Calibrate Position Sensor

ATTENTION

The Position Sensor is factory calibrated. Under normal operation it does not require
calibration.

Sensor calibration may be necessary due to any of the following conditions:

The sensor output is incorrect,

The position sensor in the actuator has been replaced,

The position sensor adjustment has been disturbed.

When the position sensor has been replaced (or serviced), you should perform a calibration of the position
sensor circuit and then store it as the motor factory calibration. Please note that performing this procedure
will destroy any previously stored motor factory calibration values. Table 29 outlines the steps to perform a
calibration to the position sensor circuit.