J. chimney termination requirements – Hearth and Home Technologies HEATILATOR SC60 User Manual

Page 30

Advertising
background image

30

A Gas

Termination

Wood or Fuel Oil Termination

B 6 in.

(152 mm) min.

20 in.

(508 mm) min.

Gas, Wood or Fuel

Oil Termination

See

illustration

above for wood

18 in.

(457 mm)

A

Gas

Termination

B

Termination Caps Staggered Height

Gas, Wood or Fuel

Oil Termination

Wood

Gas

Fuel Oil

Termination

20 in. min. *

(508 mm)

Termination Caps Same Height

* If using decorative cap cover(s), this distance may
need to be increased. Refer to the installation instruc-
tions supplied with the decorative cap cover.

See

illustration

above for wood

Slanted Roofs

Flat Roofs

Chimney must
extend 3 ft (.9 m)
above the roof

Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney

Chimney must
extend 3 ft (.9 m)
above the roof

Chimney must extend 2 ft (.6 m)
above any portion of the roof or
adjacent structures within
10 ft (3 m) of the chimney

Termination Requirements

Multiple Chimney Locations

Figure 8.10 Multiple Chimney Locations

J. Chimney Termination Requirements

• Install a cap approved and listed for this fi replace system.
• Locate cap where it will not become plugged by snow or other materials.
• Locate cap away from trees or other structures.
• The bottom of the termination cap must be at least 3 ft (.91 m) above the roof AND at least 2 ft (.61 m) above any portion

of roof within 10 ft (3.05 m) as shown in Figure 8.10.

• The distance required between caps is shown in Figure 8.10.

Heatilator • SC60 • 32838 Rev X • 10/08