Shrouds, A. radiation shield, B. field constructed shrouds – Hearth and Home Technologies HEATILATOR SC60 User Manual

Page 35

Advertising
background image

35

3 in. (76 mm) tall legs

Ø 17 1/2 in. (444.5 mm) Round Hole to fit over cap

Length x Width to fit inside shroud

Figure 10.1 Radiation Shield

10

10

Shrouds

• Chase top shrouds may be fi eld constructed where

permitted by regional building codes.

WARNING! Risk of Fire! Shrouds must be constructed
as specifi ed. Improper construction may overheat chase
top.

NOTICE:

Some regional codes require an agency-Listed

shroud. Consult your local building offi cials.

• Hearth & Home Technologies Inc. supplies UL listed

shrouds. See your dealer for details.

• The

following

fi eld constructed shroud designs have

been tested for Hearth Technologies fi replace systems
and termination caps.

• The shrouds must be constructed from a minimum .018

in. (26 ga) thick aluminized steel.

A. Radiation Shield

• Some shrouds require a radiation shield. Use where

specifi ed.

• Radiation shield must be constructed of minimum 26 ga

sheet metal.

3 in (76 mm)
minimum

Min.

Base Dim.

Min.

Base Dim.

Min.

Top Dim.

Min.

Top Dim.

Min. Opening

Width

Min. Opening

Width

Figure 10.2 Open Top Shroud Dimensions

B. Field Constructed Shrouds

• The wire mesh is optional but recommended and must

be .018 in. thick minimum, 1/2 in. mesh.

Heatilator • SC60 • 32838 Rev X • 10/08

TS345

TR342

TR342/344TV

Min. Base Dims.

in

23 x 23

28 x 28

26 x 26

mm

584 x 584

711 x 711

660 x 660

Radiation Shield

Required

Min. Top Dims.

in

20 x 20

25 x 25

23 x 23

mm

508 x 508

635 x 635

584 x 584

Min. Opening Width

in

17 x 17

22 x 22

20 x 20

mm

432 x 432

559 x 559

508 x 508

Open Top Shroud (TR342 caps require radiation shield)