Step 5 – HP Teco MA7200 Plus User Manual

Page 4

Advertising
background image

MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________

______________________________________________________________

TECO – Westinghouse Motor Company

4

•

Press the RUN key, and check the fan direction of rotation. If the direction is not correct, press
the STOP key and wait until the fan has come to a complete STOP. Next, power down the
inverter.

Danger

After the power has been turned OFF, wait at least 5 minutes until the charge
indicator extinguishes completely before touching any wiring, circuit boards or
components.

•

Reverse any two of the fan motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next,
following STEP 2, power-up the inverter; the motor direction should now be correct.



Step 5

– Select Method of Control

•

Before selecting the method of control, verify that the inverter is in the STOP mode.

•

There are two methods of control or combinations thereof that may be selected; Keypad and
Analog Signal.


RUN / STOP Command - Can be provided from the keypad or from an external contact
(see Fig. 2a).

Speed Reference – Can be from the keypad or from an external analog signal (0 – 10 VDC or
4 – 20 mA). see Fig’s 3a,3b, and 3c.

•

The RUN/STOP method of control is set by parameter Sn – 04 and the Speed Reference is set
by parameter Sn – 05. The following table shows the values to be set when selecting.

Value

Start / Stop

Sn – 04=

Speed Reference

Sn – 05=

*0 Keypad

Keypad

1

External Contact

External Analog

*

NOTE

The factory default for Sn – 04 and Sn – 05 is set to 0; Digital Operator (Keypad) No

further parameter changes are necessary if this is the desired method of control. If
External Contact
set to Sn – 04 or External Analog set to Sn – 05 is desired then proceed
as follows.