PP38+ Pellet Stove

3-90-08422R33_06/13

venting

requirements for terminating the venting
warning:
Venting terminals must not be recessed into a

wall or siding.
note: Only approved pellet vent pipe, wall pass-throughs,

and fire stops should be used when venting through

combustible materials.
note: Always take into consideration the effects of the

prevailing wind direction or other wind currents that may

cause flyash and/or smoke when placing the termination of

the vent.
in addition, the following must be observed:
A. The clearance above grade must be a minimum of 18".
B. The clearance to a window or door that may be opened

must be a minimum of 48" to the side, 48" below the

window/door, and 12" above the window/door.

(

with

outside air installed, 18” to the side or below)

C. A 12" clearance to a permanently closed window is

recommended to prevent condensation on the window.

D. The vertical clearance to a ventilated soffit located above

the terminal within a horizontal distance of 2 feet (60 cm)

from the center-line of the terminal must be a minimum

of 18".

E. The clearance to an unventilated soffit must be a minimum

of 12".

F. The clearance to an outside corner is 11" from center of

pipe.

G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90 cm) above

a gas meter/regulator assembly when measured from the

horizontal center-line of the regulator.

I. The clearance to service regulator vent outlet must be a

minimum of 6 feet.

J. The clearance to a non-mechanical air supply inlet to the

building or the combustion air inlet to any other appliance

must be a minimum of 48”.

K. The clearance to a mechanical air supply inlet must be a

minimum of 10 feet.

(

with outside air installed, 6 feet )

L. The clearance above a paved sidewalk or a paved

driveway located on public property must be a minimum

of 7 feet.

M. The clearance under a veranda, porch, deck or balcony

must be a minimum of 12 inches.

(

b. also applies)

note: The clearance to vegetation and other exterior

combustibles such as mulch is 36” as measured from the

center of the outlet or cap. This 36” radius continues to grade

or a minimum of 7 feet below the outlet.
Certain Canadian and/or Local codes or regulations may

require different clearances.
A vent shall not terminate directly above a side-walk or

paved driveway which is located between two single family

dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is fully

open on a minimum of 2 sides beneath the floor.

note: where passage through a wall, or partition of

combustible construction is desired, the installation

shall conform to can/csa-b365. (if in canada)