Caution – Falcon SG5K-2T User Manual

Page 14

Advertising
background image

12

G
N
D

L
1

L
1

L
2

L
2

240 Vdc

+

UTILITY INPUT OUTPUT TO NEXT BANK

BATTERY

Battery Disconnect &

Circuit Breaker

Input/Battery

Terminal Block

CAUTION

Reference the torque

specifications in this

manual prior to making

terminal block

connections.

COOLING FAN

DO NOT BLOCK

Reference the Leveling

Feet adjustment

procedure

USE ONLY THE WIRE

GAUGE & TYPE

REFERENCED IN THE

PRECEEDING WIRING

TABLE

For all Input/Output

wiring

USE COPPER

CONDUCTORS ONLY

AC Input Voltage --- 208-240 Vac
AC Input Current --- 4.5A max
Charger Current --- 3.9A
DC Output Voltage --- 240 Vdc
DC Output Current --- 30A

SG5 & 6kVA Extended Battery Bank Rear Panel Details

(Hardwire Model Shown)

Note: Input and output wiring must meet the National Electrical Code, ANSI/NFPA70. Please refer to the wire Gauge
table on page 6 for minimum wire gauge. THIS UNIT MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN.

CAUTION

To reduce the risk of fire, connect only to a circuit provided with a "branch rated" over-current protection device in
accordance with the National Electrical Code, ANSI/NFPA 70.