Installation Instructions for All Models Except Hardwire

1.0

UPS Input & Output Requirements.

Note: All SG Series UPS models, except Hardwire models, may be installed by

anyone providing the specified outlet, circuit and circuit protections are
available. Other plug and receptacle configurations are available, please
reference page 14 or contact the factory should an unlisted configuration e
required..

MODEL

REQUIRED REQUIRED INPUT

RECEPTACLE

CIRCUIT BREAKER

SG5K-1TXC - 120Vac, 50/50Hz, 38.7A, 1 phase, 3 wire

L5-50R

50A

SG5K-2TC - 208-240Vac, 50/60Hz, 19.5A, 1 phase, 3 wire

L6-30R

30A

SG5K-2TXC - 208-240Vac, 50/60Hz, 20.3A, 1 phase, 3 wire

L6-30R

30A

SG6K-2TC - 208-240Vac, 50/60Hz, 23.4A, 1 phase, 3 wire

L6-30R

30A

SG6K-2TXC - 208-240Vac, 50/60Hz, 24.3A, 1 phase, 3 wire

L6-30R

30A

2.0.

UPS Output Details

Note: The outputs of the referenced SG 5 & 6kVA models are not configured for 208

or 240Vac split-phase operation. Output 1 (208-230Vac) is powered directly
from the UPS inverter while Output 2 (120Vac) is created from the inverter
output, through an isolation transformer. A new neutral for the 120Vac output
is derived at the output of the transformer. This configuration provides the
advantage of providing the full rated output of the UPS at output 1, output 2, or
a combination of both.

MODEL

STANDARD OUTLET

FUSES

CONFIGURATION

Class CC

SG5K-1TXC

Output 1: 208, 220, 230 or 240Vac selectable, 3500W*

(1) L6-30R

(2) KLKD 30

Output 2: 115, 120, 125 or 130Vac, (follows output 1), 3500W*

(2) Duplex 5-20R (2) KLKD 20

SG5K-2TC

Output 1: 208, 220, 230 or 240Vac selectable, 3500W

(1) L6-30R

(2) KLKD 30

Output 2: None

SG5K-2TXC

Output 1: 208, 220, 230 or 240Vac selectable, 3500W*

(1) L6-30R

(2) KLKD 30

Output 2: 115, 120, 125 or 130Vac, (follows output 1) 3500W*

(2) Duplex 5-20R (2) KLKD 20

SG6K-2TC

Output 1: 208, 220, 230 or 240Vac selectable, 4200W

(1) L6-30R

(2) KLKD 30

Output 2: None

SG6K-2TXC

Output 1: 208, 220, 230 or 240Vac selectable, 4200W*

(1) L6-30R

(2) KLKD 30

Output 2: 115, 120, 125 or 130Vac, (follows output 1) 4200W*

(2) Duplex 5-20R (2) KLKD 20

* Maximum load at outputs 1 & 2.

All UPS outputs are protected by fuses. Always replace these fuses with the same
type and rating.

13

To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the

specified "branch rated" over current protection device in accordance with the National Electrical

Code, ANSI/NFPA 70.