28

Electrical Input

Nominal AC Voltage

120V

230V

230V

120V

230V

230V

AC Voltage Range

87-140V

170-275V

170-275V

87-140V

170-275V

170-275V

Current-Amps

38.7

20.3

19.5

46.6

24.3

23.4

Frequency

50/60 Hz ±5%

Efficiency (Typical)

> 79%

> 82%

> 79%

> 82%

Power Factor Correction

> 0.95

Electrical Output

Watts

3500

4200

AC Voltage

(Switchable except where noted)

120 & 208V or
120 & 220V or
120 & 240V

(No Switching)

(1)

120V

(1)
(1)

208V
220V
230V
240V

208V
220V
230V
240V

120 & 208V or
120 & 220V or

120 & 240V

(No Switching

)

(1)

120V

(1)
(1)

208V
220V
230V
240V

208V
220V
230V
240V

Isolation Transformer

No

Yes

No

No

No

Yes

No

No

Frequency

60Hz

50/60Hz

50/60Hz

50/60Hz

60Hz

50/60Hz

50/60Hz

50/60Hz

Voltage Regulation

±4%

±3%

±4%

±3%

Frequency Stability

± 0.3% (Battery Mode)

Step Load Change

±7% for 100% load variation

THD – Linear Loads

< 3%

THD – Non-Linear Loads

< 7%

<5%

< 7%

<5%

Overload

105% for 50 Seconds

Crest Ratio

3:1

(1) Contact the factory for output settings.
.

Battery

DC Voltage

240V

Type

12V, 7AH Sealed Lead Acid Maintenance-Free

Back Up Time @ Full Load
@ 1/2 Load

9 Minutes

28 Minutes

7 Minutes

18 Minutes

Recharge Time

10 Hours to 90%

Battery times are approximate.

Electrical Connections Input

-1TX

Hardwire

Hardwire

-1TXC

L5-50P

-2T

Hardwire

Hardwire

-2TC

L6-30P

L6-30P

-2TX

Hardwire

Hardwire

-2TXC

L6-30P

L6-30P

Electrical Connections Output

-1TX

Hardwire

Hardwire

-1TXC

(2) duplex

5-20R &

(1) L6-30R

-2T

Hardwire

Hardwire

-2TC

(1) L6-30R

(1) L6-30R

-2TX

Hardwire

Hardwire

-2TXC

(2) duplex

5-20R &

(1) L6 -30R

(2) duplex

5-20R &

(1) L6-30R

Contact the factory for other input/output options.

Environmental

Operating Temperature

0º C to 35º C (32º F to 95º F)

Humidity

10% to 95% Non – Condensing

Altitude

7,000 Feet

Cooling

Low Velocity Forced Air Fans

Audible Noise @ 1 Meter

< 55dBA

Controls and Indicators

LED

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level

Audible Alarms

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm

Communications

RS-232 Serial Port (Bundled UPSilon 2000 Software)

Mechanical

Dimensions H x W x D i nches
(mm)

Hardwired Models
Receptacle Models

32.1 x 10.2 x 21.8 (815.3 x 259.0 x 553.7)

32.1 x 10.2 x 27.0 (815.3 x 259.0 x 685.8)

Weight lb. (kg)

T
TX
TC
TXC

216 (98)

299 (136)
239 (108)

322 (146)

Agency Listing

UL1778, CUL,

FCC Class A

-2T: UL1778, CUL, FCC Class A, CE

All others:

UL1778, CUL, FCC Class A

UL1778, CUL,

FCC Class A

-2T: UL1778, CUL, FCC Class A, CE

All other s:

UL1778, CUL, FCC Class A

Model Number

SG5K -1TX & -

-1TXC

SG5K -2TX &

-2TXC

SG5K -2T

& -2TC

SG6K-1TX

SG6K-2TX &

-2TXC

SG6K-2T

& -2TC

Nominal VA

5000

5000

5000

6000

6000

6000

Available Options: Extended Run Time Battery Packs, Make-Before-Break Maintenance Bypass, SNMP/HTTP Network Card,
Frequency & Voltage Conversion.

©

2004 Falcon

®

Electric, Inc. All rights reserved. Falcon

®

and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.

All other brand names and trademarks are the property of their respective owners.
The information and specifications stated in this document are subject to change without notice.

Advertising
This manual is related to the following products: