Installation Instructions For Hardwire Models (see model numbers referenced below)

1.0

UPS Input & Output Requirements.

Note: All SG Series hardwire UPS models must be installed by a licensed
electrician, in accordance with the National Electrical Code (NEC) ANSI/NFPA70
and all local regulations. It is further required that the input of SG Series hardwire
UPS be wired to a building service panel incorporating a dedicated “branch
rated” circuit breaker of the proper rating.

MODEL

REQUIRED INPUT

CIRCUIT BREAKER

SG5K-1TX:- 120Vac, 50/50Hz, 38.7A, 1 phase, 3 wire

50A

SG5K-2T - 208-240Vac, 50/60Hz, 19.5A, 1 phase, 3 wire

30A

SG5K-2TX - 208-240Vac, 50/60Hz, 20.3A, 1 phase, 3 wire

30A

SG6K-1TX - 120Vac, 50/60Hz, 46.6A, 1 phase, 3 wire

70A

SG6K-2T - 208-240Vac, 50/60Hz, 23.4A, 1 phase, 3 wire

30A

SG6K-2TX - 208-240Vac, 50/60Hz, 24.3A, 1 phase, 3 wire

30A

WIRE GAUGE CHART

MODEL

AC INPUT

-1 = 120 Vac

-2 = 208-240 Vac

AC OUTPUT(S)

120 Vac 208-240 Vac

EXTERNAL

BATTERY

240 dc

SG5K-1TX

8 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

12 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

SG5K-2T

12 Awg. 600V

75

°

C CU

N/A

12 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

SG5K-2TX

12 Awg. 600V 75

°

C

CU

10 Awg. 600V

75

°

C CU

12 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

SG6K-1TX

6 Awg. 600V

75

°

C CU

8 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

SG6K-2T

10 Awg. 600V

75

°

C CU

N/A

10 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

SG6K-2TX

10 Awg. 600V 75

°

C

CU

8 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

10 Awg. 600V

75

°

C CU

External Battery &
Charger System

16 Awg, 600V

75

°

C CU

N/A

N/A

10 Awg. 600V

75

°

C CU

SCREW TORQUE SPECIFICATIONS FOR

INPUT/OUTPUT WIRING BLOCK

UPS & BATTERY BANK

Wire Gauge

Torque

(inch pounds)

18 - 10 Awg.

20

8-6 Awg

25 - 30

ONLY USE WIRE WITH SOLID COPPER CONDUCTORS FOR ALL INPUT/OUTPUT/BATTERY WIRING

CAUTION

To reduce the risk of fire, connect only to a circuit providing over-current protection incorporating the

specified "branch rated" over-current protection device in accordance with the National Electrical

Code, ANSI/NFPA 70.

IMPORTANT

INPUT REQUIREMENTS

7